The main objective of this post is to creating both Lighting Protection plan & grounding system plan with a good knowledge of standard references.
NFPA 780 (Lightning Protection) BRIEF.
A) Air terminals height 0.6 m along edge (within 0.6 m from roof edge) with 7.6 m maximum spacing. Air terminals height 0.6 m with maximum spacing of 15 m. [4.8.2.1], [4.8.3].
B) 45 m maximum length of cross-run conductor permitted without a connection from the cross-run conductor to the main perimeter or down conductor.[4.8.3].
C) Two Down-conductors Minimum for any shaped structure with maximum spacing is 30m .If run coursed on or in reinforced concrete columns or on structural steel columns shall be connected to the reinforcing steel or the structural steel member at their upper and lower extremities with maximum 60 m vertical spacing.[4.9.10.1].
D) Bare looping minimum size is 58mm.sq for class II AND 29mm.sq for class I, WHILE 25X3mm(or 70mmsq )typically used.
E) Ground rods shall be not less than 12.7 mm in diameter 2.4 m long and extend vertically not less than 3 m into the earth with minimum spacing 6 m.[4.13.23].
F) Ground Ring Electrode directly contact with the earth, consist at least 6m of bare copper conductor not smaller than 35mmsq. [NEC2011,250.52(A)(4)] with minimum depth 4.6m below grade shall be connected to steel columns around the perimeter of the structure at intervals averaging not more than 18 m.[4.16.4.1].
G) Loop Ground conductor is commonly used is 120 mm.sq.
H) Grounding Electrode Conductor as per shown NEC table 250.66.
I) Considered Sphere radius is 46.0 m.[4.7.4].
J) The following figures for typical plans of the systems.
K) The following figures showing the Reference NEC for GROUNDING cable sizing.